Certification

Circuit Protection Selection Guidance

Circuit protection devices have existed since 1864; one would think that selection of circuit protection would be a straight forward task. However, it is not. NASA developed a seven-step process for circuit protection selection and both EN3179 and AS50881 provide some guidance.

In a past article, Lectromec began to consider the differences between two major EWIS standards in aerospace; AS50881 and EN3197. This article reviews these standards and how they address circuit protection selection.

EN3197

EN3197 contains good guidance on selection criteria and principles to achieve a safe and properly functioning system.

Criteria

The following are important criteria to live by when selecting the correct part for circuit protection:

System Level Guidance

For a circuit protection device to work effectively, it must trip prior to reaching the maximum component current rating. For example, if it is determined that the maximum current allowed on a cable for a given time duration is given by the curve in red in the figure, then the circuit breaker tripping curve should be at a lower current threshold everywhere along the curve. The most sensitive (lowest maximum current rating) EWIS component in the system should set the expected circuit protection performance. To do this analysis, one needs to determine the wire’s/cable’s current carrying capacity that can be carried through different wire and cable harness designs.

AS50881
Circuit breaker trip curves in relation to maximum cable carrying capacity.

Specific Failure Mode Guidance

There are several failure modes defined and considered in EN3197 whose effect on the system may be mitigated by appropriate circuit protection. Possible failure phenomena are defined in EN3197 are shown in the table below. Mitigation of many of these failure modes are handled by wire selection and wires are required to be specifically tested. The test methods generally call for thermal breaker type circuit protection, but other circuit protection technologies are acceptable [link].

Circuit protection selection and wire selection should go hand in hand to mitigate risk. System level testing is invaluable in determining the system failure event behavior. The test methods associated on the arcing phenomena are generally focused on wire selection and not on circuit protection selection; this could be an area of improvement in both standards. In addition to aiding in circuit protection selection, the test standard could be established to certify performance.

Failure Mode

Relation to Circuit Protection

Short Circuit

Circuit protection should trip in the event of a hard short.

Wet Short Circuit:

Wire selection and testing is used generally to mitigate the effect of this type of failure in the circuit. Thermal breakers are used as the circuit protection device.

Wet Arc Tracking:

If a breach in the insulation is near a breach on an adjacent line, moisture can be a means of conduction between the lines. This can occur for long periods of time without tripping the circuit protection and can also develop into a more violent arcing scenario.

Dry Arc Tracking

This can be caused by vibration of an exposed wire conductor with a conducting structure. It may not trip a conventional circuit breaker or may take a long time to trip causing significant damage.

Circuit Protection Selection Guidance

The EN3197 test method also provides guidance on many of the possible circuit protection technologies that may be used in the system. These include the following: circuit breakers, arc fault circuit interrupters, arc fault circuit breakers, remote control circuit breakers, solid state circuit breakers, residual current circuit breakers, and fuses [described here link].

These technologies have been developed to mitigate varying failure possibilities in the system. Arc fault circuit breakers, for example, can significantly decrease the duration of an electric arc compared to conventional circuit breakers thereby greatly limiting the arc damage risk [link].

AS50881 Circuit Protection Guidance

In contrast, AS50881 has sparse guidance on circuit protection that may be summed up as follows:

AS50881 could benefit substantially from guidance found in EN3197.

Conclusion

Modern circuit protection technologies can provide considerable benefits including mitigation of potential failure risk. Those seeking guidance on the best practices in selection of circuit protection should consider reviewing the applicable sections in the EN 3197 standard. Further, the AS50881 could benefit from incorporation of guidance included in the European standard.

Tristan Epp Schmidt
Tristan Epp Schmidt
Engineer, Lectromec

Since starting at Lectromec in early 2015, Tristan has been key in many of test and assessment wire systems assessment projects wire systems assessment. His attention to detail has lead to several key insights in Lectromec's research initiatives.