2021 25.1701 25.1703 abrasion AC 33.4-3 AC 43 Accelerated Aging accessibility ADMT Aging Systems AIR6808 AIR7502 Aircraft Power System aircraft safety Aircraft Service Life Extension Program (SLEP) altitude Aluminum arc damage Arc Damage Modeling Tool Arc Fault (AF) Arc Fault Circuit Breaker (AFCB) Arc Resistance Arc Track Resistance Arcing Arcing Damage AS22759 AS22759/87 AS23053 AS29606 AS4373 AS4373 Method 704 AS50881 AS5692 AS6019 AS6324 AS81824 AS83519 AS85049 AS85485 AS85485 Wire Standard ASTM B230 ASTM B355 ASTM B470 ASTM D150 ASTM D2671 ASTM D495 ASTM D8355 ASTM D876 ASTM F2639 ASTM F2696 ASTM F2799 ASTM F3230 ASTM F3309 ATSRAC Attenuation Automated Wire Testing System (AWTS) Automotive Avionics backshell batteries bend radius Bent Pin Analysis Best of Lectromec Best Practice bonding Cable Cable Bend cable testing Carbon Nanotube (CNT) Certification cfr 25.1717 Chafing Chemical Testing Circuit Breaker circuit design Circuit Protection cleaning clearance Coaxial cable cold bend collision comparative analysis Compliance Component Selection Condition Based Maintenance Conductor Conductor Testing conductors conduit Connector connector installation Connector rating connector selection connector testing connectors contacts Corona Corrosion Corrosion Preventing Compound (CPC) corrosion prevention Cracking creepage D-sub data analysis data cables degradat Degradation Delamination Derating design safety development diagnostic Dielectric breakdown dielectric constant Dimensional Life disinfectant Distributed Power System DO-160 dry arc dynamic cut through E-CFR electric aircraft Electrical Aircraft Electrical Component Electrical Power Electrical Testing Electrified Vehicles Electromagnetic Interference (EMI) Electromagnetic Vulnerability (EMV) Electrostatic Discharge EMC EMF EMI EN2235 EN3197 EN3475 EN6059 End of Service Life End of Year Energy Storage engines Environmental Environmental Cycling environmental stress ethernet eVTOL EWIS certification EWIS Component EWIS Design EWIS Failure EWIS sustainment EWIS Thermal Management EZAP FAA FAA AC 25.27 FAA AC 25.981-1C FAA Meeting failure conditions Failure Database Failure Modes and Effects Analysis (FMEA) FAQs FAR FAR 25.1703 FAR 25.1707 FAR 25.1709 Fault fault tree Filter Line Cable Fixturing Flammability fleet reliability Flex Testing fluid exposure Fluid Immersion Forced Hydrolysis fuel system fuel tank ignition Functional Hazard Assessment functional testing Fundamental Articles Fuse Future Tech galvanic corrosion Glycol Gold Gold plating Green Taxiing Grounding hand sanitizer handbook Harness Design harness protection hazard Hazard Analysis health monitoring heat shrink heat shrink tubing high current high Frequency high speed data cable High Voltage High Voltage Degradation HIRF History Hot Stamping Humidity Variation HV connector HV system ICAs IEC 60851 IEC60172 IEEE immersion insertion loss Inspection installation installation safety Instructions for Continued Airworthiness insulating material insulating tape Insulation insulation breakdown insulation resistance insulation testing interchangeability IPC-D-620 ISO 17025 Certified Lab ISO 9000 J1673 Kapton Laser Marking life limit life limited parts Life prediction life projection Lightning lightning protection liquid nitrogen lithium battery lunar Magnet wire maintainability Maintenance Maintenance costs Mandrel mean free path measurement mechanical stress Mechanical Testing MECSIP MIL-C-38999 MIL-C-85485 MIL-DTL-17 MIL-DTL-23053E MIL-DTL-3885G MIL-DTL-38999 MIL-E-25499 MIL-F-5372 MIL-HDBK MIL-HDBK-1646 MIL-HDBK-217 MIL-HDBK-454 MIL-HDBK-516 MIL-HDBK-522 MIL-HDBK-525 MIL-HDBK-683 MIL-STD-1353 MIL-STD-1560 MIL-STD-1798 MIL-STD-464 MIL-T-7928 MIL-T-7928/5 MIL-T-81490 MIL-W-22759/87 MIL-W-5088 MIL–STD–5088 Military 5088 modeling moon MS3320 NASA NEMA27500 Nickel nickel plating No Fault Found OEM off gassing Outgassing Over current Overheating of Wire Harness Parallel Arcing part selection Partial Discharge partial discharge at altitude Performance physical hazard assessment Physical Testing polyamide polyimdie Polyimide-PTFE Power over Ethernet power system Power systems predictive maintenance Presentation Preventative Maintenance Program Probability of Failure Product Quality PTFE pull through Radiation Red Plague Corrosion Reduction of Hazardous Substances (RoHS) regulations relays Reliability Research Resistance Revision C Rewiring Project Risk Assessment S&T Meeting SAE SAE Committee Sanitizing Fluids Scrape Abrasion Secondary Harness Protection separation separation distance Separation Requirements Series Arcing Service Life Extension Severe Wind and Moisture-Prone (SWAMP) Severity of Failure shelf life Shield Shielding Shrinkage signal signal cable Silver silver plated wire silver-plating skin depth skin effect Small aircraft smoke Solid State Circuit Breaker Space Certified Wires Splice standards Storage stored energy superconductor supportability Sustainment System Voltage Temperature Rating Temperature Variation Test methods Test Pricing Testing testing standard Thermal Circuit Breaker Thermal Endurance Thermal Index Thermal Runaway Thermal Shock Thermal Testing tin Tin plated conductors tin plating tin solder tin whiskering tin whiskers top 5 Transient Troubleshooting TWA800 UAVs UL94 USAF validation verification video Visual Inspection voltage voltage differential Voltage Tolerance volume resistivity vw-1 wet arc white paper whitelisting Winding wire Wire Ampacity Wire Bend Wire Certification Wire Comparison wire damage wire failure wire performance wire properties Wire System wire testing Wire Verification wiring components work unit code

The Impact of a Short Circuit on Conductor Performance

Testing & Assessment

Key Takeaways
  • The assumption is that circuit protection should prevent damage to system wiring.
  • Testing was conducted to determine if repeat short circuit events would increase conductor resistance.
  • Tests found no appreciable conductor resistance change after several short circuit events.

Over-current and shorting are an ever-present risk to power wires and cables. The hope is that circuit protection can quickly respond to over-current conditions fast enough to prevent any damage to the circuit components. Wire conductors have a temperature rating, limited by the plating, because that is the established temperature for long-term reliability. But what happens when a single wire is exposed to repeat over-current conditions? Does the latest generation of circuit protection sufficiently protect the wiring?

In a recent set of tests, Lectromec examined the impact of over-current conditions on wire conductivity. These tests sought to determine if repeat over-current conditions would result in a measurable resistance increase. The background of these tests, the test setup, and the results are discussed here.

Similar Tests

For any testing to be conducted, it is important to find an existing test that closely matches the conditions to be evaluated. The obvious benefit is to compare the results against an existing set of tests carried out as part of product qualification. The SAE AS4373 contains standards for tests that are used for product qualification and which are similar to those conducted in this evaluation. For example, Time to Smoke and Smoke Resistance are crucially different in the properties being evaluated as well as the practical conditions each test aims to simulate.

In the Time to Smoke test (AS4373 Method 507), amperage increases are applied to the current in 5A steps until smoke is observed. The circuit resistance is changed in order to achieve the desired increase in current.

In the Smoke resistance (AS4373 Method 513) test, a resistance value for the test wire at an elevated temperature is estimated based on the wire’s physical properties. The current is adjusted to achieve this resistance and temperature and the wire is held at these conditions for 15 minutes. Though the wire’s resistance is considered in this test, it is representative of a much longer-term latent fault within a circuit.

Both existing tests look for visible damage (smoke) due to a slow, long-term increase in current/ temperature while in use. No SAE standard currently exists for measuring the effects on a wire conductor due to a rapid change in current/ temperature such as a short circuit/fault condition.

Test Set-up

In an effort to evaluate the possible effects a short circuit fault condition may have on a typical wire, Lectromec carried out a series of experiments. This experiment was performed on a 20ft sample of 20AWG AS22759/34 wire.

The sample wire was connected on one end through one of Lectromec’s arc track resistance test units to a generator, with the other end of the sample connected to the neutral return. The Lectromec arc cabinet provided a means for a controlled change of current between trials by selecting the desired circuit resistance. The short circuit duration was limited by a 7.5A thermal circuit breaker.

A data logger was connected to the circuit and recorded the current output during each trial.

Results

Tests were conducted at five different currents increasing the current applied in each trial. Prior to testing and after each trial, the wire’s resistance was measured by following the AS4373 Method 403 for conductor resistance.

The recorded data allowed for the determination of each trial’s duration and maximum current. One may note that test duration decreases with an increase of current, as the thermal circuit breaker reacts more quickly to the higher temperature created by high current events.

In-Series Resistance (Ω) (not including connecting wires)

Current Peak (A)

Test Duration(ms)

Resultant Wire Resistance (Ω)

Pre Test – Initial Resistance Measurement

0.094

2.0

73

583

0.094

1.5

93.7

293

0.096

1.0

121

201

0.095

0.5

190

89

0.095

0.0

345

30

0.094

0.0

356

663

0.093

0.0

377

706

0.093

Two tests at the maximum current (the second and third trials with in-series resistance of 0.0 Ohms) were run without circuit protection, leaving them to remain at the fault condition for a longer duration. The extended duration provided insight into the effects such a fault condition may have on an unprotected circuit wire. Those extended tests represent a total of more than 40 times longer exposure to over-current conditions.

Summary

Lectromec determined that there was no appreciable long-term change to the conductor resistance due to repeated short circuit faults. A thermal circuit breaker will successfully protect the wiring in a circuit during a fault event. Even when exposed to the fault condition for a longer duration at high current, the wire showed no significant change in resistance.

It is useful to note that AS22759/34 wire used is tin plated, meaning that it has a lower temperature rating than silver or nickel plated wire. It is safe to say that these materials, rated for higher temperatures, would similarly remain unaffected when subject to a short circuit fault condition.

While it is possible that additional high current cycling might degrade the conductor performance, seven high current events yielded no appreciable change during this evaluation. For those seeking an ISO accredited laboratory to support your aircraft evaluation needs, contact Lectromec.

Laura Wishart

Laura Wishart

Engineer, Lectromec

Laura has been with Lectromec since 2019 and has been a key contributor on projects involving testing of EWIS/fuel system failure modes, the impact of poor installation practices on EWIS longevity, and wire/cable certification testing. Her knowledge and attention to detail ensure consistent delivery of accurate test results from Lectromec’s lab.